Powerflex Specifications

POWERFLEX (FLEXIBLE SINGLE POWER CORES)

APPLICATION

This highly flexible range of power cable can be used as a convenient replacement for the less flexible solid SANS class 2 cores.

This makes it easier to loom in confined spaces such as PANELS.

The inner dielectric consists of general purpose PVC bonded to the outer nitrile PVC sheath which has excellent water, oil as well as abrasion resistant properties allowing for further use in borehole pumps and engine rooms.

MOST OFTEN USED BY

Electricians, electrical contractors, D.I.Y enthusiasts.

SPECIFICATION SABS 1574-3

x
Voltage Rating
600/1000 volts
Spark Test Voltage
6000 volts (rms)
Current Rating
as per table below
Conductor
Annealed PCW class 5.
Temperature Range
-10 to + 70 °C
Insulation
General purpose PVC D3 as per SABC 1411 P2
Sheathing
Nitrile PVC (coloured) D6 as per SABS 1411 P 2
Colours
Any colour as per customer

PACKAGING

100 m shrink-wrapped coils or on 500 to 1000 m length wooden drums

TECHNICAL DATA

Size - (mm²) - mm² Individual wire OD - Nom. mm Nom. Core diameter - mm Mass - kg/100m Current Rating (1-Phase) - A Current Rating (3-Phase) - A
16
0.34
9.8
22
76
68
25
0.34
11.0
29
101
89
35
0.34
12.0
39
125
110
50
0.34
14.6
56
151
134
70
0.34
17.1
81
192
171
95
0.34
19.0
105
232
207
120
0.34
21.6
134
269
239
150
0.34
22.5
154
350
322
185
0.34
25.5
192
440
404

Maximum conductor temperature 70°C ; ambient air temperature 30°C
Current Ratings as per SANS 10142-1:2005 Table 6.2(a) Installation Method 2