FLAT TWIN AND EARTH

(FTE)

flat twin earth cable fte

DESCRIPTION

Conductor
Insulation
Earth Conductor
Sheath
Solid annealed copper (to SABS 1411 Part 1)
General purpose PVC (to SABS 1411 Part 2 - D5)
Solid annealed BARE copper
General purpose PVC

APPLICATION

General purpose Household and Industrial wiring :- Under roof, under floor and under plaster.

MOST OFTEN USED BY

Electricians, electrical contractors.

PROPERTIES

Voltage Rating
Temperature Range
Core Colours
Sheath Colours
Conductors
300/500 volts
-10 to + 70 °C
Red & Black (To SANS 1411 Part 2)
White & Black (To SANS 1411 Part 2)
High Conductivity annealed solid conductors. Manufactured to SANS 1411 Part1

PACKAGING

100m shrink-wrapped coils
1,000m drums or reels

TECHNICAL DATA

Core Size
Phase
mm²
1
1.5
2.5
4
6
10
Core Size
Earth
mm²
1.00
1.00
1.50
1.50
2.50
4.00
Current Rating
Current Rating
A
14
18
25
30
39
54
Volt Drop
Volt Drop
mV/A/m
30.0
28.0
18.0
10.8
7.0
4.4
Major Axis
Major Axis
mm
7.4
8.4
10.0
12.0
13.2
16.5
Minor Axis
Minor Axis
mm
4.1
4.6
5.2
6.3
6.9
8.2
Mass
Mass
kg/100m
4.1
4.6
5.2
6.3
6.9
8.2

Table 6.3a SANS 10142
Continuous operation at 70°C ; ambient air temperature 30°C

error: Content is protected !!